Heating and Cooling System Configurations for Commercial Buildings

Michael Tobias
6 Minutes Read
  • Home
  • Blog
  • Heating and Cooling System Configurations for Commercial Buildings

    In commercial buildings, HVAC loads normally represent the highest energy expense. Geographic location plays a significant role: buildings far to the north or south of the world typically have high heating expenses, while those located in the tropics may require air conditioning all year long.

    Just like in residential settings, there is a broad range of heating and cooling options for commercial buildings, each with advantages and limitations. Three of the most commonly used systems for commercial buildings are:

    • Variable-air-volume (VAV) systems with a packaged rooftop unit
    • Chiller, cooling tower and boiler systems
    • Water-source heat pump systems with a cooling tower and boiler

    Are you planning a commercial real estate project? Get a professional HVAC design.

    Contact Us


    1) VAV System with Packaged Rooftop Unit

    shutterstock_1502627030Packaged rooftop units (RTUs) normally include a condenser for air conditioning, and a gas or electric boiler for space heating. In climates where the unit must provide air conditioning with low outdoor humidity, it is also possible to add an economizer, which reduces the cooling load on the condenser. In all modes of operation, fans are used to blow air into a duct system that distributes it among the separate indoor zones.

    • Each zone has a variable-air-volume (VAV) box with a damper that opens and closes according to cooling or heating needs.
    • Damper position is controlled based on the temperature set point of each specific zone. For example, the damper will fully open if a specific zone requires maximum cooling or heating output.

    Traditional VAV systems suffer a drastic reduction in energy efficiency when subject to part load conditions: if all building zones are at partial load with their dampers half-closed, duct pressure increases and the system may become noisy. In addition, the extra pressure represents wasted fan power. However, it is possible to achieve excellent results through the use of automation and variable frequency drives:

    • A control system constantly assesses the state of all VAV boxes. Ideally, at least one of them should be fully open; otherwise, fan power is being wasted.
    • If none of the dampers is fully open, fan speed is reduced and all dampers are opened gradually until one of them reaches the fully open position.
    • At this point, the fan is providing just the right airflow for the current HVAC load.

    There can be considerable savings on fan power when speed is controlled through a variable frequency drive. In general, fan power is proportional to speed cubed – a fan running at 90% speed only consumes around 73% of the energy it would consume at full speed. An added benefit of speed control is that noise is drastically reduced.

    VAV systems with packaged rooftop units are practical in facilities that have a large rooftop area in proportion to their indoor floor space, given that air is the main medium used to transport heat. These systems are not practical in multi-story buildings due to the limited rooftop area and the long vertical distances involved; systems based on water-cooled chillers or water-source heat pumps are preferred in these applications.

    2)Chiller with Cooling Tower and Boiler

    shutterstock_135110642These systems use water as a medium to deliver or extract heat, and water circuits pass through air-handling units (AHUs) that provide the required airflow for each building zone.

    • In cooling mode, the chiller extracts heat from the cold water circuit that circulates through the building, and rejects it into a secondary water loop that is connected to the cooling tower. The cooling tower then rejects the heat outdoors.
    • In heating mode, the circulating water passes through a boiler. Most boilers are powered by electricity, gas or oil.

    In both cases, heat is exchanged between the circulating water and the indoor air at the AHUs. If the chiller and boiler share a water circuit (two-pipe system), the entire building must operate in either heating or cooling mode; however, when there is a separate water circuit for each mode of operation (four-pipe system), simultaneous heating and cooling can be provided to different zones. Of course, a four-pipe system is more expensive because piping and accessories are essentially doubled.

    Just like in the case of VAV systems, it is possible to achieve considerable savings with control and automation:

    • Modern chillers typically come with variable-speed compressors, which can operate efficiently even under part-load conditions. Some models combine speed control with staged operation to further enhance efficiency.
    • Variable speed drives can be used for multiple system components, including cooling tower fans, water pumps and air-handling units.
    • There are also economizers for water-cooled systems, but they only apply for specific climate zones, where the system will provide air conditioning with low outdoor humidity.

    Chiller-based systems typically offer a higher efficiency than VAV systems, and are also more practical for multi-story buildings: rather than having several packaged rooftop units, it is possible to consolidate the system into a single chiller and cooling tower, and only the cooling tower has to be located outdoors or on the rooftop.

    3) Water-Source Heat Pump System with a Cooling Tower and Boiler

    shutterstock_306105035Commercial HVAC systems based on water-source heat pumps tend to be the superior choice in terms of versatility and energy efficiency. Heat pumps are based on the refrigeration cycle, just like air conditioners, but they offer reversible operation; when multiple heat pumps are used to serve separate areas of a commercial building, they can switch between cooling and heating modes as needed.

    • All heat pumps in a building share a common water circuit, and they will either reject or absorb heat depending on the needs of each zone.
    • Since the water circuit it shared, equal heating and cooling loads balance each other out.
    • If the cooling load is higher, a cooling tower is used to reject the extra heat; on the other hand, if the heating load is higher, a boiler is used to compensate for the difference.

    Just like in the two previous scenarios, it is possible to make the system even more efficient by adding speed control to all pumps and fans used. Heat pumps are among the most efficient heating and cooling systems in the market: they can match or surpass the efficiency of a chiller in cooling mode, and in most cases they can provide space heating with less than 40% of the energy consumption of a resistance heater.

    The need to install a dedicated heat pump for each building zone drives up the cost of these systems, but this is compensated in the long term thanks to the superior energy efficiency achieved. For example, if there is a moment when cooling and heating loads are equal, this system can operate with both the boiler and cooling tower deactivated.

    Conclusions

    One of the most important design choices in a commercial building is HVAC configuration, since this system represents a significant portion of ownership costs in the long term. Building layout is an important consideration: low-height facilities with ample rooftop areas tend to favor packaged rooftop units with VAV systems, while multi-story buildings tend to favor the use of chillers or water-source heat pumps.

    Of course, there are viable energy efficiency enhancements that can be deployed in all cases. Modulating the speed of compressors, pumps and fans is more energy-efficient than cycling these pieces of equipment on and off, and it also contributes towards a longer service life and reduced maintenance expenses.

    Contact Us

    Tags : Design Construction
    Linkedin

    Join 15,000+ Fellow Architects and Contractors

    Get expert engineering tips straight to your inbox. Subscribe to the NY Engineers Blog below.

    Have a project in mind?
    Request a proposal